Close the gate valve before the pressure reducing valve and open the gate valve after the pressure reducing valve to create a low pressure environment downstream;
Rotate counterclockwise to the uppermost position (relative to the lowest outlet pressure) and close the rear gate valve of the pressure reducing valve;
Slowly open the gate valve in front of the pressure reducing valve until it is fully open;
Slowly rotate the adjusting screw clockwise to adjust the outlet pressure to the required pressure (based on the gauge pressure behind the valve); after adjustment, tighten the locking nut and open the gate valve behind the pressure reducing valve;
If the outlet pressure is higher than the set pressure during adjustment, it must be readjusted, that is, it can only be adjusted from low pressure to high pressure.