Direct and reverse action of pneumatic actuators. If the push rod of a pneumatic actuator moves downward as the input air pressure increases, it is termed "direct-acting"; if the push rod moves upward, it is termed "reverse-acting."

 

Direct and reverse mounting of control mechanisms. There are two ways to arrange a valve plug within a valve body: direct mounting and reverse mounting. A valve is considered "directly mounted" if the downward movement of the valve plug results in a decrease in the flow cross-sectional area between the plug and the valve seat; conversely, it is "reverse-mounted" if such movement leads to an increase in the flow area. Notably, for a dual-guided directly mounted valve, the configuration can be converted to a reverse-mounted one simply by connecting the valve stem to the lower end of the valve plug. Typically, valves with a nominal diameter (DN) of less than 25 mm utilize a single-guided design and are therefore available only in a directly mounted configuration.

 

Operating modes of pneumatic actuators. Pneumatic actuators are classified as either "air-to-open" or "air-to-close." If a valve opens as the signal pressure increases, it is "air-to-open"; if it closes as the signal pressure increases, it is "air-to-close." Since both the actuator and the control valve (when equipped with a dual-guided plug) can be either direct-acting or reverse-acting, the "air-to-open" or "air-to-close" characteristic of a pneumatic actuator is determined by the combination of these factors.